Double solenoid valve
DN 25, DN 50 nominal diameters
DMV 50025
DMV 50050
Technical description
The DUNGS double solenoid valve DMV integrates two solenoid valves in one compact fitting.
- Automatic shut-off valves as per DIN EN
161 Class A Group 2.
- Two A valves in one housing
- Double seat valves
- High flow rates
- Max. operating pressure up to 5.0 bar
(500 kPa)
- Fast closing
- Fast opening
- DC solenoid
- Low electric power consumption through power switching
- Compact, light-weight
Application
Double solenoid valves are used where two single valves were mounted previously. In connection with DUNGS gas regulators and additional components, a wide variety of regulating tasks can be performed.
Suitable for gases of families 1, 2, 3 and other neutral gaseous media.
Approvals
EC type testing certificate as per:
• EC-Gas Appliances Regulation
• EC-Pressure Equipment Directive
Approvals in other important gas consuming countries
Specifications
Nominal diameters
Flange
DN 25 50
Connection flange as per DIN 2501 Part 1, to fit preweld flanges as per DIN 2633
(PN 16) DN 25 - DN 50, ISO 7005 - 1 (PN 16), ISO 7005 - 2 (PN 16)
Construction length as per DIN 3202 Part 1, row F1 for DN 50
Max. operating pressure
5000 mbar (500 kPa)
max. pressure difference ∆p = 500 mbar
max. flow velocity = 50 m/s
Solenoid valve V1
Automatic shut-off valve as per EN 161: Class A, Group 2,
Version: double-seat
Solenoid valve V2
Automatic shut-off valve as per EN 161: Class A, Group 2,
Version: double-seat
Closing time
< 1 s
Opening time
< 1 s
Materials of gas conveying parts
Housing:
aluminium, steel, no non-ferrous metals
Seals at valve seat:
NBR basis, suitable for gases as per G260/l
Ambient temperature
-15 °C bis +60 °C
Installation position
Solenoid vertically upright to lying horizontally
Dirt trap
Sieve installed. To protect the complete gas train we recommend you to install
an upstream gas filter
Measuring gas connection
G 1/4 DIN ISO 228 centrally upstream of V1 and downstream of V2
G 1/4 DIN ISO 228 between V1 and V2
Voltage/frequency
50 - 60 Hz, 230 V AC, -15% +10%, further voltages on request
Other preferred voltages: 110 V - 120 V AC, 24 V DC
Rating / power consumption
Version
Starting power
approx. [W]
Holding power
approx. [W]
Break-away
starting current
[A]
Holding
current [A]
at 230 V AC, + 20 °C
All indications are effective values
Power supply display
Green LED
Degree of protection / switch-on
duration
IP 54 as per IEC 529 (EN 60529)
Switching cycles
60 per hour (30 s on/off)
Electrical connection
At screw terminals via PG 11
Plug connection as per DIN 175 0301-803 can be retrofitted
Radio interference
Degree of interference N